ControlLoopHealthEvents¤

Health of a control loop from its setpoint and actual value (and optionally the controller output), independent of setpoint changes: error integrals per window, oscillation of the control error, output saturation, and a per-shift grade.

ts_shape.events.engineering.control_loop_health · Engineering guide · API reference

Example¤

import numpy as np
import pandas as pd
from ts_shape.events.engineering.control_loop_health import ControlLoopHealthEvents

t = pd.date_range("2024-01-01", periods=8 * 3600, freq="1s")
pv = 50 + 0.8 * np.sin(np.arange(len(t)) / 30)  # hunting loop
df = pd.concat([pd.DataFrame({"systime": t, "uuid": u, "value_double": v}) for u, v in [
    ("flow_sp", np.full(len(t), 50.0)), ("flow_pv", pv), ("valve_out", np.clip(60 + 50 * (50 - pv), 0, 100))]])

loop = ControlLoopHealthEvents(df, setpoint_uuid="flow_sp", actual_uuid="flow_pv", output_uuid="valve_out")
integrals = loop.error_integrals(window="1h")
saturation = loop.output_saturation(upper_limit=100.0, lower_limit=0.0, window="1h")
result = loop.loop_health_summary(window="8h")
print(result[["iae", "bias", "oscillation_count", "saturated_pct", "health_grade"]])

Methods¤

All arguments are keyword-only.

Method Returns (per window)
error_integrals(window='1h', max_gap=None) iae, ise, itae, bias, sample_count
detect_oscillation(window='5min', min_crossings=4) oscillating windows: crossing_count, estimated_period_seconds, amplitude, damping_direction
output_saturation(upper_limit=100.0, lower_limit=0.0, window='1h') time_at_high_pct, time_at_low_pct, time_saturated_pct, longest_saturation_seconds (needs output_uuid)
loop_health_summary(window='8h', oscillation_window='5min', min_crossings=4) iae, bias, oscillation_count, saturated_pct, health_grade

Notes¤

  • Error = actual − setpoint (all signals from value_double); a positive bias means the process runs above setpoint.
  • error_integrals with max_gap=None weights each error by the time since the previous sample. With max_gap each error is held until the next sample and longer intervals contribute nothing, so a communication gap is not integrated as one large error.
  • Output samples within 1 % of the upper_limit − lower_limit range of a limit count as saturated. Without output_uuid, output_saturation returns an empty frame.
  • loop_health_summary detects oscillation in oscillation_window slices (a whole shift would almost always have enough zero-crossings) and counts the episodes starting in each report window. health_grade counts issues (IAE above 1.5 × the median IAE of all windows, any oscillation, more than 5 % saturated): good with none, fair with one, poor with more.