PowerIntegrator¤

Integrates an instantaneous active-power signal (kW, e.g. *.Total_Active_Power-kW) into energy (kWh) per window, weighting each sample by how long it was valid. Use it when instantaneous power is all you have; if the meter also has a cumulative kWh register, the counter difference per window is billing-accurate and needs no integration.

ts_shape.transform.calculator.power_integration · Engineering guide · API reference

Example¤

import numpy as np
import pandas as pd
from ts_shape.transform.calculator.power_integration import PowerIntegrator
from ts_shape.events.energy.consumption_analysis import EnergyConsumptionEvents

t = pd.date_range("2024-01-01 06:00", periods=240, freq="1min")
df = pd.DataFrame({"systime": t, "uuid": "press7:Total_Active_Power-kW",
                   "value_double": np.where(np.arange(240) % 60 < 45, 140.0, 20.0)})

result = PowerIntegrator.energy_by_window(df, window="1h", max_gap="15min")
print(result[["start", "kwh", "avg_kw", "coverage"]])
deltas = PowerIntegrator.to_energy_deltas(df, window="1h", max_gap="15min")
daily = EnergyConsumptionEvents(deltas).consumption_by_window("press7:Total_Active_Power-kW", window="1D")

Methods¤

All are static and keyword-only after the frame.

Method Returns
energy_by_window(df, window='1h', method='locf', max_gap=None, total=True) per window: start, end, kwh, avg_kw, coverage, sample_count (+ uuid with total=False)
to_energy_deltas(df, window='1h', ...) the same energy in the standard schema: systime, uuid, value_double (kWh), is_delta; feeds the energy detectors
segment_energy(df, window='1h', ...) per-sample contributions (audit trail): window_start, start, end, kw_start, kw_end, kwh

Notes¤

  • Summing kW samples scales with the logging rate, and a plain mean is a sample-count average; on irregular historian data both are wrong. Over a full hour the kWh equal the time-weighted mean kW.
  • method="locf" (default) holds each value until the next sample, correct for on-change PLC and meter logging. method="linear" is trapezoidal, correct for a smooth analog signal on a fixed cycle; on a 0 → 100 kW ramp over one hour linear gives exactly 50 kWh and locf slightly less.
  • Always set max_gap on historian data: without it one 500 kW sample before a three-hour outage counts 1500 kWh. A segment longer than max_gap is dropped and counts towards neither energy nor coverage. Set the cap above the normal logging cadence; an on-change signal on a steady machine can be silent for a long time.
  • coverage is the fraction of the window backed by data (with total=True, the least-covered signal's). Windows with no data are omitted, never reported as 0 kWh. avg_kw = kwh / covered hours.
  • kwh is net energy: negative power (PV export, regenerative drives) is integrated as-is.
  • total=True integrates each signal separately and sums them, which is the plant total (averaging power across machines would not be). to_energy_deltas keeps the signal UUIDs by default (total=False); with total=True the summed series is named event_uuid (default energy:kwh).
  • power_unit="W" or "MW" for differently scaled signals; the result is always kWh. A -kW suffix is only a naming convention, so compare a full day with the meter's own counter.